The Remote DP Sensor has been designed for cleanroom operations with an IP67 rated housing and easy field service features. The Remote DP Sensor combines a flexible field selectable range, output and calibration options. A local display allows for cleanroom personnel to easily identify room specifications before entering sterile rooms.
。4 to 8 Selectable Field Ranges
。Enhanced Sensor Protection
。Simple On-site Installation
。Wall, Cabinet or Duct Mounted
。Cleanroom Wipe Down
。Local Display
。IP67 Enclosure
。2 Year Warranty
Performance Data | DP-0.5 | DP-1.0 |
---|---|---|
Field Selectable Ranges (Bidirectional) |
±0.1” WC (±25 Pa) ±0.25” WC (±50 Pa) |
±0.1“ WC (±25 Pa) ±0.25” WC (±50 Pa) Model for Higher Pressure Applications ±0.5“ WC (±100 Pa) ±1.0” WC (±250 Pa) ±2.5” WC (±500 Pa) ±5.0” WC (±1,000 Pa) |
Accuracy Scale Long Term Stability (max.) |
±0.5% Full Scale 1.0% FS/YR |
±1.0% Full Scale 2.0% FS/YR |
Physical Description | ||
Case | Fire-Retardant Polycarbonate (UL 94 V-0 Approved), Hinged Lid | |
Display | 4 Digit LCD | |
Mounting | Wall/DIN or Duct Mounting | |
Electrical Connection Block | Removable Screw Terminal | |
Pressure Fitting | 3/16” O.D. Barbed Brass | |
Zero | Push Button | |
Span | Push Button | |
Weight (approx.) | 8 Ounces | |
Environmental Data | ||
Operating Temperature | 32 to 122°F (0 to 50°C) | |
Electrical Data | ||
Excitation Range |
13 to 30 VDC/18 to 24 VAC (Voltage Output) 13 to 30 VDC (4 to 20mA output at terminals) |
|
Current Consumption | 30mA (max) | |
Mis-Wiring | Reverse Excitation Protection | |
Field Selectable Output | 0 to 5 V, 0 to 10V (3-wire), 4 to 20mA (2-wire) | |
Output Resistance (Voltage Output) | 10 Ohms (max) | |
Load Resistance (Voltage Output) | 10 K-Ohms (min) | |
Loop Resistance (4-20mA) | 0 to 800 Ohms | |
Approval | CE & RoHS Compliant |
• electronics industry , R&D institute
• Pharmaceutical , hospital , food and beverage. cosmetic manufacturing